基于子系统划分和注入电流比的配电网故障定位方法
CSTR:
作者:
作者单位:

华南理工大学电力学院,广东 广州 510006

作者简介:

李 浩(1998—),男,硕士研究生,研究方向为配电网故障定位;E-mail: 202020114145@mail.scut.edu.cn 张禄亮(1988—),男,通信作者,博士,副教授,研究方向为电力系统继电保护、电能质量、负荷监测、风速预测等。E-mail: epzhangll@scut.edu.cn

通讯作者:

中图分类号:

基金项目:

广东省自然科学基金面上项目资助(2022A 1515011587);国家自然科学基金面上项目资助(52077081)


Fault location method for a distribution network based on subsystem division and injection current ratio
Author:
Affiliation:

School of Electric Power Engineering, South China University of Technology, Guangzhou 510006, China

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    针对配电网因结构复杂、分支众多而难以实现准确故障定位的问题,提出了一种基于子系统划分和注入电流比的配电网故障定位方法。首先,根据末端节点数将配电网划分成若干相互独立的子系统,并在任意子系统内计算首末端节点的等效虚拟注入电流,继而可得故障点的注入电流。然后,假设将该电流在各子系统的不同节点分别注入,根据末端节点电压计算值与实测值的误差大小确定故障子系统。最后,在故障子系统内,利用首末端节点注入电流比与真实故障点的位置关系进行故障定位。所提方法仅需在首末端节点配置微型同步相量测量单元,具有较好的经济性。经Matlab/Simulink仿真测试,所提方法不仅受故障类型、过渡电阻、故障位置、初相角的影响较小,而且对负荷变化和噪声不敏感。

    Abstract:

    It is difficult for a distribution network to achieve accurate fault location because of its complex structure and many branches. Thus this paper proposes a distribution network fault location method based on subsystem division and injection current ratio. First, the network is divided into several independent subsystems according to the number of end nodes, and the equivalent virtual injection current of the head and end nodes is calculated according to any subsystem, and then the injection current of the fault point can be obtained. Then, assuming that the current is injected from different nodes of each subsystem, the fault subsystem is determined according to the error between the calculated value and the measured value of the end node voltage. Finally, in the fault subsystem, the relationship between the injection current ratio of the head and end nodes and the position of the real fault point is used to locate the fault. The proposed method only needs to configure a micro synchronous phasor measurement unit (μPMU) at the head and end nodes. This method has good economy. Through Matlab/Simulink simulation tests, the proposed method is not only less affected by fault type, transition resistance, fault position and fault initial phase angle, but is also insensitive to load variation and noise.

    参考文献
    相似文献
    引证文献
引用本文

李 浩,张禄亮,栾云飞,等.基于子系统划分和注入电流比的配电网故障定位方法[J].电力系统保护与控制,2023,51(8):63-72.[LI Hao, ZHANG Luliang, LUAN Yunfei, et al. Fault location method for a distribution network based on subsystem division and injection current ratio[J]. Power System Protection and Control,2023,V51(8):63-72]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2022-08-01
  • 最后修改日期:2022-10-25
  • 录用日期:
  • 在线发布日期: 2023-04-11
  • 出版日期:
文章二维码
关闭
关闭