This paper introduces a model based fault analysis method for six-phase transmission system. Using basic symmetry properties of six-phase transmission line, this paper firstly transforms the impedence matrix to two uncoupled three-phase systems, and then calculates the two systems with asymmetrical fault analysis method respectively, finally does asymmetrical short-circuit calculation after composing the two systems into six-phase compound sequence system.