放电间隙异常对准稳态情况下500 kV母差保护的影响分析
CSTR:
作者:
作者单位:

(1.国网江苏省电力有限公司检修分公司,江苏 南京 211102;2.许继集团有限公司,河南 许昌 461000; 3.国网江苏省电力有限公司南京供电公司,江苏 南京 210019)

作者简介:

刘怀宇(1991—),男,硕士,工程师,研究方向为继电保护及自动装置原理及二次回路;E-mail: liuhuaiyu6@ 163.com 邓迎君(1975—),男,通信作者,硕士,高级工程师,研究方向为智能变电站通信技术和保护产品的研发测试;E-mail: zsb_dengyingjun@163.com 陈 昊(1980—),男,博士,研究员级高级工程师,研究方向为电力系统保护与控制。E-mail: Pingfengma@ 126.com

通讯作者:

中图分类号:

基金项目:

国家自然科学基金项目资助(51807028)


Analysis of the influence of 500 kV bus-bar differential protection in a quasi-steady state caused by a discharge gap anomaly
Author:
Affiliation:

(1. Maintenance Branch of State Grid Jiangsu Electric Power Co., Ltd., Nanjing 211102, China; 2. XJ Group Corporation, Xuchang 461000, China; 3. Nanjing Power Supply Company of State Grid Jiangsu Electric Power Co., Ltd., Nanjing 210019, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    分析了一起因电流互感器二次接线盒内放电间隙金属片短接引起的保护电流回路缺陷。基于保护电流回路图,搭建等效电路模型。同时对在准稳态情况下因放电间隙金属片短接所引起的流入500 kV母差保护电流分流情况进行基础理论分析。在此基础上结合简化等效电路模型搭建Pspice电路仿真模型,进一步阐释此异常对500 kV母差保护装置采样电流的影响。最后结合500 kV母差保护逻辑,在准稳态情况下分析放电间隙异常对500 kV母差保护功能的影响。

    Abstract:

    A protection current circuit defect, which is caused by the short connection of a discharge gap metal sheet in the secondary junction box of a current transformer, is analyzed in this paper. Based on the protection current circuit diagram, the equivalent circuit model is presented. At the same time, the current shunt of 500 kV bus-bar differential protection in a quasi-steady state, caused by the short connection of a discharge gap metal sheet, is analyzed theoretically. On this basis, combined with the simplified equivalent circuit model, a circuit simulation model is built by the Pspice. Then, the influence of this anomaly on the sampling current of a 500 kV bus-bar differential protection device is further highlighted. Finally, combined with the protection logic of 500 kV bus-bar differential protection, the influence of a discharge gap anomaly on 500 kV bus-bar differential protection function is analyzed in a quasi-steady state. This work is supported by National Natural Science Foundation of China (No. 51807028).

    参考文献
    相似文献
    引证文献
引用本文

刘怀宇,邓迎君,陈 昊,等.放电间隙异常对准稳态情况下500 kV母差保护的影响分析[J].电力系统保护与控制,2020,48(21):173-178.[LIU Huaiyu, DENG Yingjun,,et al. Analysis of the influence of 500 kV bus-bar differential protection in a quasi-steady state caused by a discharge gap anomaly[J]. Power System Protection and Control,2020,V48(21):173-178]