基于改进LMD方法的电压骤降检测与分析
CSTR:
作者:
作者单位:

(1.大唐国际发电股份有限公司陡河发电厂,河北 唐山 063000;2.国网徐州供电公司,江苏 徐州 221078; 3.东南大学电气工程学院,江苏 南京 210096)

作者简介:

郑文光(1994—),男,硕士研究生,工程师,研究方向为电能质量检测与控制;E-mail:tmac132180suqian@ 163.com
张加岭(1990—),男,通信作者,硕士研究生,工程师,研究方向为电能质量分析与控制;E-mail:957631183@ qq.com
邢 强(1992—),男,博士研究生,研究方向为电能质量检测与治理。E-mail:997330668@qq.com

通讯作者:

中图分类号:

基金项目:

国家重点基础研究发展计划项目资助(2016YFB 0101800)


Voltage sag detection and analysis based on a modified LMD method
Author:
Affiliation:

(1. Datang International Power Generation Co., Ltd. Douhe Power Plant, Tangshan 063000, China;2. State Grid Xuzhou Electric Power Company, Xuzhou 221078, China;3. School of Electrical Engineering, Southeast University, Nanjing 210096, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    随着新能源并网技术的普及和发展,大量非线性装置接入电网对其电能质量产生了一定影响,因此有必要对电能质量进行检测和分析。针对现有检测识别方法存在抗噪性和精确性不足的问题,提出一种改进的LMD方法。该方法首先对自适应分解方法筛选过程的机理进行研究,分析了极值点拟合分布程度容易受到高频间断信号干扰,提出对原始信号先加入受控高斯白噪声再进行LMD分解。其次针对特征参数提取部分存在端点能量泄漏问题,提出采用经验调制分解方法对瞬时参数进行检测的方式。通过仿真实验表明所提方法可以有效抑制模态混叠和端点效应。最后搭建了电压骤降实验平台,运用实测数据验证了所提方法能够准确提取电压骤降的各个扰动参数,从而为电能质量扰动分析提供了一种新思路。

    Abstract:

    With the popularization and development of new energy grid-connected technology, the large number of non-linear devices connected to the power grid have an impact on its power quality. Thus it is necessary to detect and analyze that impact. To help overcome the shortcomings of existing detection and recognition methods in anti-noise and accuracy, a modified LMD method is proposed in this paper. This approach first studies the mechanism of the selection process for the adaptive decomposition method, and then analyzes the degree of extreme point fitting distribution that is susceptible to high frequency and intermittent signal interference. It uses the noise-assisted decomposition method to add controlled Gaussian white noise to the original signal and then perform LMD decomposition. Then, taking into account end-point energy leakage in the feature parameter extraction, an empirical modulation decomposition method is proposed to detect instantaneous parameters. Simulation results show that the proposed method is able to effectively suppress mode mixing and endpoint effects. Finally, experimental data from the built power quality disturbance platform demonstrates that the proposed method is capable of accurately extracting all disturbance parameters of voltage sag. This also provides a novel method for power quality disturbance analysis. This work is supported by National Key Basic Research Program of China (No. 2016YFB0101800).

    参考文献
    相似文献
    引证文献
引用本文

郑文光,张加岭,邢强.基于改进LMD方法的电压骤降检测与分析[J].电力系统保护与控制,2020,48(11):119-127.[ZHENG Wenguang, ZHANG Jialing, XING Qiang. Voltage sag detection and analysis based on a modified LMD method[J]. Power System Protection and Control,2020,V48(11):119-127]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2019-07-02
  • 最后修改日期:2020-01-24
  • 录用日期:
  • 在线发布日期: 2020-05-27
  • 出版日期:
文章二维码
关闭
关闭