基于异质元胞自动机的互联电网连锁故障控制措施
CSTR:
作者:
作者单位:

(山东科技大学电气与自动化工程学院,山东 青岛 266590)

作者简介:

于 群(1970—),男,博士,教授,研究方向为电力系统安全分析和电力系统继电保护;E-mail:yuqun_70@ 163.com
王 琪(1995—),男,通信作者,硕士研究生,研究方向为电力系统运行与控制。E-mail:15698150706@163.com

通讯作者:

中图分类号:

基金项目:

国家电网公司2018年科技项目资助(XTB 17201800166)“基于多沙堆理论的互联电网停电事故预警技术及系统研发”


A control measure for interconnection power grid cascading failure based on heterogeneous cellular automata
Author:
Affiliation:

(College of Electrical Engineering and Automation, Shandong University of Science and Technology, Qingdao 266590, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为减少互联电网停电事故的规模及频率,提出了一种基于异质元胞自动机的互联电网连锁故障控制措施。首先,依据互联电网由多个不同特性的区域电网构成这一实际,并考虑区域电网间相互影响,建立了异质元胞自动机的互联电网连锁故障模型。其次,考虑各区域电网特性和不同故障阶段区域间的协调关系,提出了一种多区域多阶段线路潮流控制措施。最后,以IEEE118节点系统作为仿真案例,采用异质元胞自动机模型进行停电事故仿真,分别从幂律分布和故障时间序列两个方面验证了控制措施的有效性。并通过与其他控制措施比较,展示了其所具有的优越性。仿真结果表明:调度人员根据各区域电网运行情况,合理选择区域间的支援系数,可有效降低各区域电网大停电风险。

    Abstract:

    To reduce the scale and frequency of blackouts in interconnected power grid, a control measure for interconnection power grid cascading failure based on heterogeneous cellular automata is proposed. Firstly, according to the fact that the interconnected power grid is composed of multiple regional power grids with different characteristics, and considering the interactions among regional power grids, the interconnection grid cascading failure model based on heterogeneous cellular automata is constructed. Then, considering the characteristics of each regional power grid and the interregional coordination relationship in different fault stages, a power flow control measure is proposed. Finally, taking IEEE118 node system as simulation case, the heterogeneous cellular automaton model is used to simulate the power failure. The effectiveness of the control measure is verified from the power law distribution and fault time series respectively, then its superiority is demonstrated by comparing it with other control measures. The simulation results show that the dispatcher can effectively reduce the blackout risk of regional power grids by reasonably selecting the interregional support coefficient according to the operation conditions of regional power girds. This work is supported by the Science and Technology Project of 2018 State Grid Corporation of China (No. XTB 17201800166) "Multi-Sand Pile Theory of Interconnection Power Grid Blackouts Early Warning Technology and System Development".

    参考文献
    相似文献
    引证文献
引用本文

于群,王琪,曹娜.基于异质元胞自动机的互联电网连锁故障控制措施[J].电力系统保护与控制,2020,48(7):118-132.[YU Qun, WANG Qi, CAO Na. A control measure for interconnection power grid cascading failure based on heterogeneous cellular automata[J]. Power System Protection and Control,2020,V48(7):118-132]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2019-05-22
  • 最后修改日期:2019-07-15
  • 录用日期:
  • 在线发布日期: 2020-03-30
  • 出版日期:
文章二维码
关闭
关闭