含源配电网的无功电压分段自适应自治控制策略
CSTR:
作者:
作者单位:

(1.广东电网有限责任公司河源供电局,广东 河源 517000;2.广州市奔流电力科技有限公司, 广东 广州 510670;3.华南理工大学电力学院,广东 广州 510640)

作者简介:

黄祖委(1987—),男,硕士研究生,工程师,研究方向为配电网运行与优化;E-mail:595033260@qq.com
高小镜(1991—),女,通信作者,硕士研究生,工程师,研究方向为配电网规划、电力系统建模仿真。E-mail:1282672838@qq.com

通讯作者:

中图分类号:

基金项目:

广东电网有限责任公司科技项目(GDKJXM 20162615);国家自然科学基金资助(51777077)


Reactive voltage control strategy based on adaptive autonomous segment for distribution network with sources
Author:
Affiliation:

(1. Heyuan Power Supply Bureau, Guangdong Power Grid Co., Ltd., Heyuan 517000, China;2. Guangzhou Power Electrical Technology Co., Ltd., Guangzhou 510670, China;3. School of Electric Power, South China University of Technology, Guangzhou 510640, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    针对分布式电源(DG)接入配电网产生的电压越限问题,可以利用DG逆变器输出的无功功率为含源配电网提供无功支撑以解决电压越限问题。提出含源配电网的无功电压分段自适应自治控制策略。首先通过采集当前时刻DG并网点电压和并网点处馈线流过的有功功率方向。然后根据采集到的信息动态自适应调整触发电压临界值,触发电压临界值将并网点电压运行值划分为五个区间。其次根据DG并网点电压所处区间使用Q(U)控制策略计算DG无功输出目标值。最后控制DG逆变器输出无功追踪该目标值。将所提方法与不考虑DG无功调控能力方案、基于定参数的Q(U)控制方案进行综合比较,仿真结果表明所提控制策略在解决电压越限问题、抑制电压扰动、提高电压质量等方面均有显著的效果。

    Abstract:

    This paper focuses on the problem that the voltage exceeds the limit range when Distributed Generation (DG) is connected to distribution network. Reactive power of DG inverter can offer reactive support to solve the voltage problem. The reactive voltage control strategy based on adaptive autonomous segment for Distribution Network with Sources (DNS) is put forward in this paper. Firstly, this strategy can adaptively adjust the trigger voltage thresholds by collecting the information about the voltage of Point of Common Coupling (PCC) of DG and the direction of active power flow through next feeder adjoining the PCC of DG. Then, the threshold value of trigger voltage is adjusted dynamically according to the collected information. The run value of the PCC of DG can be divided to five intervals by the trigger voltage thresholds. Secondly, according to the interval that the voltage of PCC of DG is in the reference values about reactive power outputs of DG inverter can be calculated by using the Q(U) control method. Finally, the reactive output of the DG inverter is controlled to trace the reference value. This research is comprehensively compared with the case without the reactive support of DG inverter and the case where DG inverter operates using the Q(U) control strategy with constant segmented voltage threshold. The simulation result shows that the proposed method has a significant improvement on reducing the voltage exceeding the limits range, restraining the voltage disturbance and improving the voltage quality. This work is supported by Guangdong Power Grid Co., Ltd. Science and Technology Project (No. GDKJXM20162615) and National Natural Science Foundation of China (No. 51777077).

    参考文献
    相似文献
    引证文献
引用本文

黄祖委,黄智鹏,杨夏,等.含源配电网的无功电压分段自适应自治控制策略[J].电力系统保护与控制,2019,47(9):10-18.[HUANG Zuwei, HUANG Zhipeng, YANG Xia, et al. Reactive voltage control strategy based on adaptive autonomous segment for distribution network with sources[J]. Power System Protection and Control,2019,V47(9):10-18]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2018-05-14
  • 最后修改日期:2018-11-06
  • 录用日期:
  • 在线发布日期: 2019-05-08
  • 出版日期:
文章二维码
关闭
关闭