一种用于校验双端行波测距装置的测试系统的研发与测试
CSTR:
作者:
作者单位:

(1.许昌开普电气研究院,河南 许昌461000;2.清华大学电机系电力系统及发电设备控制和仿真 国家重点实验室,北京 100084)

作者简介:

王 伟(1972—),男,高级工程师,现从事电力系统仿真试验研究;E-mail:wangwei@ketop.cn
吴亚辉(1988—),男,硕士研究生,工程师,现从事电流互感器高频特性建模和暂态保护测试研究;
李志勇(1986—),男,硕士研究生,工程师,现从事电力系统仿真试验研究工作。

通讯作者:

中图分类号:

基金项目:

国家重点研发计划基金资助(2016YFB0900600)


Development and test of a test system for verifying double-ended traveling wave fault location equipment
Author:
Affiliation:

(1. Xuchang Ketop Electric Research Institute, Xuchang 461000, China;2. State Key Lab of Control and Simulation of Power System and Generation Equipments, Department of Electrical Engineering, Tsinghua University, Beijing 100084, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    双端行波测距技术利用故障行波的初始波头抵达故障线路两端的时间差来实现故障定位,比单端测距和传统测距技术有着较高的精度和可靠性。双端行波测距装置在投入运行前必须经过专门的校验和测试,这是传统的继电保护测试仪所不能做到的。提出了一种用于校验该装置的测试系统的设计实现方案,并对系统样机做了大量的实验测试。实验结果表明,该测试系统的电压、电流输出具有很高的频率精度、幅值精度和同步性,满足双端行波测距装置的校验需求。

    Abstract:

    The double-ended traveling wave fault location technology uses the time difference between the initial wave head of the fault traveling wave to achieve fault location, and has higher accuracy and reliability than single-ended and traditional fault location techniques. The double-ended traveling wave fault location equipment must undergo special check and test before putting into operation, this is what the traditional relay protection tester can't do. This paper presents a design and implementation scheme for a test system which is used to verify the equipment, and a large number of experimental tests are performed on the prototype. The experimental results show that the voltage and current output of the test system have high frequency accuracy, amplitude accuracy and synchronism, which can meet the verification requirements of the double-ended traveling wave fault location equipment. This work is supported by National Key Research and Development Program of China (No. 2016YFB0900600).

    参考文献
    相似文献
    引证文献
引用本文

王伟,吴亚辉,李志勇,等.一种用于校验双端行波测距装置的测试系统的研发与测试[J].电力系统保护与控制,2019,47(3):176-181.[WANG Wei, WU Yahui, LI Zhiyong, et al. Development and test of a test system for verifying double-ended traveling wave fault location equipment[J]. Power System Protection and Control,2019,V47(3):176-181]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2018-03-11
  • 最后修改日期:2018-05-30
  • 录用日期:
  • 在线发布日期: 2019-01-30
  • 出版日期:
文章二维码
关闭
关闭