基于模型识别的消弧线圈接地系统单相接地选线方法
CSTR:
作者:
作者单位:

(1.国网河南省电力公司电力科学研究院, 河南 郑州 450052;2.西安科技大学电气与控制工程学院,陕西 西安 710054;3.西安交通大学电气工程学院,陕西 西安 710049;4.河南恩湃电力技术有限公司,河南 郑州450000)

作者简介:

徐铭铭(1985—),男,博士,工程师,研究方向为配电网运行分析;E-mail:xu_ming_ming@vip.sina.com
高淑萍(1970—),女,讲师,博士,主要研究方向为电力系统继电保护;E-mail:gao.sp2003@163.com
常仲学(1991—),男,通信作者,博士研究生,研究方向为电力系统继电保护。E-mail:changzhx@163.com

通讯作者:

中图分类号:

基金项目:

国家电网公司科技项目“考虑人身安全防护的配电网单相接地故障快速处理关键技术研究”


Model recognition based single-phase earthed faulty line selection method of Petersen coil grounded system
Author:
Affiliation:

(1. State Grid Henan Electric Power Research Institute, Zhengzhou 450052, China;2. School of Electrical and Control Engineering, Xi’an University of Science and Technology, Xi’an 710054, China;3. School of Electrical Engineering, Xi’an Jiaotong University, Xi’an 710049, China;4. Henan EPRI Electric Technology Co., Ltd., Zhengzhou 450000, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    基于模型识别的继电保护思想提出了一种消弧线圈接地系统单相接地故障选线新方法。在特征频带内将线路等效成电容模型,首先利用故障暂态信号通过最小二乘方法求解出各出线的电容初值,然后用故障稳态信号求解电容值并与电容初值比较。由于故障线路不符合所建立的电容模型,模型误差较大;健全线路基本符合所建立的电容模型,模型误差接近于0,基于此特点就可以实现故障线路的识别。该方法具有自举性,通过仿真和录波数据验证了所提方法的有效性。

    Abstract:

    A new method of faulty line selection method based on model recognition for Petersen coil grounded system is presented. The equivalent circuit of every line is modeled as capacitance during fault characteristic frequency band. The initial value of capacitance is calculated by transient information through least square fitting. Then capacitance value calculated by the steady-state signal is compared with the initial value. It is found that fault line does not meet the established capacitance model and model error is large; while the sound line is basically in accordance with the established capacitance model and the model error is close to zero. Based on these characteristics, faulty line selection criteria is constructed. This method has a bootstrap characteristic. Simulation and field recording data show that the proposed method is feasible. This work is supported by Science and Technology Project of State Grid Corporation of China “Research of Key Technologies for Fast Handling of Distribution Network Single-phase Grounding Fault Considering Personal Safety Protection”.