Impact of the CT saturation of the delta winding on the HVDC protection and its countermeasure
Author:
Affiliation:

(1. State Grid Hubei Electric Power Research Institute, Wuhan 430077, China; ;2. State Grid Zhejiang Electric Power Research
Institute, Hangzhou 310000, China; ;3. State Key Laboratory of Advanced Electromagnetic Engineering and Technology
(Huazhong University of Science and Technology), Wuhan 430074, China; ;4. Electric Power Security and High
Efficiency Laboratory (Huazhong University of Science and Technology), Wuhan 430074, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为提高直流换流器桥差保护的可靠性,防止其在交流系统发生短路故障、励磁涌流等扰动期间误动,提出了一种换流器桥差保护应对CT饱和的方法。理论分析与数字仿真表明,YD换流变阀侧三角形绕组在交流扰动期间流过零序环流将导致桥差保护出现虚假动作电流,引发保护误动作。对此问题,提出了通过引入三角形绕组零序环流作为制动量的桥差保护防误动策略,并利用零序环流与桥差电流出现的相对时间差,判断是否投入该防误动策略。仿真表明,该方法能够在提高桥差保护在交流系统扰动期间可靠性的同时,不影响桥差保护对于内部故障的灵敏度与动作速度。

    Abstract:

    In order to improve the reliability of the bridge differential protection for the DC converter, prevent the misoperation of the protection during short-circuit fault and the inrush current, the countermeasure for the CT saturation of the YD converter transformer of the bridge differential protection is proposed. The theoretical analysis and the simulation test disclose that the CT saturation in the delta winding of the YD converter transformer during the disturbance of the AC system will cause the false operation current, resulting in the misoperation. To solve this problem, the paper proposes a countermeasure that introducing the zero-sequence circulating current as the restraint current of the bridge differential protection. The time difference between the increase of the zero-sequence circulating current and the rise of the bridge differential current is utilized to determine whether to apply the proposed countermeasure. The simulation tests indicate that this countermeasure can improve the reliability of the bridge differential protection during the disturbance in the AC system, and meanwhile would not affect the sensitivity and the speed of the bridge differential protection for the internal fault.