基于2 M业务的电网保护恢复机制研究
CSTR:
作者:
作者单位:

(1.国网咸宁供电公司,湖北 咸宁437000;2.国网湖北省电力公司,湖北 武汉430077;3.中国电力工程
顾问集团中南电力设计院有限公司,湖北 武汉430071;4.武汉大学电子信息学院,湖北 武汉 430072)

作者简介:

李建明(1972-),男,硕士研究生,主要从事电网安全生产方面管理工作;E-mail:lijm1616@163.com
刘 媛(1983-),女,硕士研究生,主要研究方向为电网通信安全;E-mail:136375731@qq.com
沈晗阳(1983-),男,硕士研究生,主要研究方向为光纤通信安全。E-mail:passhy@163.com

通讯作者:

中图分类号:

基金项目:

国家自然科学基金(50677047);湖北省自然科学基金(2015CFB563)


Research on the protection mechanism of electric power grid based on 2 M business
Author:
Affiliation:

(1. Hubei Xianning Power Supply Company, Xianning 437000, China; ;2. State Grid Hubei Electric Power Company,
Wuhan 430077, China; ;3. Central Southern China Electric Power Design Institute, Wuhan 430071, China;
;4. School of Electronic Information, Wuhan University, Wuhan 430072, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    针对电网控制普遍采用SNCP(subnetwork connection protection)自愈环保护方式所面临的问题,提出了在电力通信光纤网络中引入ASON(Automatically Switched Optical Network)智能技术。采用网状网组网方式提高网络生存能力,实现端到端业务的快速配置和部署,对网络路由进行动态的优化调整,提高网络管理的智能化水平和网络资源利用率;研究了保证自愈切换时,电网控制业务恢复算法业务传送收发路径完全一致性的通道恢复路由拆建协议,实现了电网控制业务的自动多路由保护和应对多点故障的能力。咸宁市供电公司试运行结果表明,所提算法能够有效增强通信网对电网控制业务的安全保障水平,提高全网络的生存性和可靠性。

    Abstract:

    In order to solve the problem of the protection mechanism SNCP (subnetwork connection protection) in power grid, this paper introduces a new technology, named ASON (Automatically Switched Optical Network) which is constructed by mesh network model, to improve the viability of the power grid. This new technology can realize the peer-to-peer business and adjust the routers dynamically. In this way, the intelligence level and resource utilization rate of the power grid network are increased. It also studies the break-before-create protocols, which keep generating the alternate routes to protect the power system and deal with multipoint failures. Commissioning results in Xianning Power Supply Company verify that the algorithm presented in this paper is effective to improve the safety level and the survivability level of the whole power system. This work is supported by National Natural Science Foundation of China (No. 50677047) and Natural Science Foundation of Hubei Province (No. 2015CFB563).

    参考文献
    相似文献
    引证文献
引用本文

李建明,刘 媛,沈晗阳,等.基于2 M业务的电网保护恢复机制研究[J].电力系统保护与控制,2016,44(16):106-111.[LI Jianming, LIU Yuan, SHEN Hanyang, et al. Research on the protection mechanism of electric power grid based on 2 M business[J]. Power System Protection and Control,2016,V44(16):106-111]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2016-01-14
  • 最后修改日期:2016-03-25
  • 录用日期:
  • 在线发布日期: 2016-08-16
  • 出版日期:
文章二维码
关闭
关闭