混合MIDC馈入下的工频变化量阻抗方向保护 动作特性分析
CSTR:
作者:
作者单位:

作者简介:

徐 岩(1976-),男,博士,副教授,硕士生导师,研究方向为电力系统保护与安全控制;E-mail: Xuyan@ ncepubd.edu.cn

通讯作者:

中图分类号:

基金项目:


Performance of impedance directional protection based on variation of power-frequency components in hybrid multi-infeed HVDC system
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    交流电网故障引发线路换相换流器高压直流(Line Commutated Converter High Voltage Direct Current, LCC-HVDC)换相失败,改变了原有交流电网工频变化量方向保护动作特性。针对这一问题,建立了由电压源换流器高压直流(Voltage Source Converter HVDC, VSC-HVDC)系统与LCC-HVDC系统组成的混合多馈入直流(bybrid multi-infeed HVDC,HMIDC)输电系统模型,并与馈入同一交流电网的单条LCC-HV

    Abstract:

    The LCC-HVDC commutation failure caused by AC power network fault affects the operation of directional protection based on power-frequency component variation for AC transmission lines. A hybrid multi-infeed HVDC system model consisted of a VSC-HVDC system and a LCC-HVDC system is set up, compared with a AC/DC system of a single LCC-HVDC system fed into the same AC grid. Combined with the characteristic of the analysis of power-frequency component variation based on the principle of directional protection, the performance of LCC-HVDC equivalent impedance of power-frequency component variation is quantitatively analyzed under the same commutation failure in LCC-HVDC system of this two different transmission structures. The simulations of two different structures for the same commutation failure of HVDC in identical fault simulated by PSCAD/EMTDC testify the accuracy and validity of the theory analysis. It indicates that the hybrid multi-infeed HVDC system can improve the impact of directional protection based on power-frequency component variation caused by the LCC-HVDC commutation failure and provides the theoretical basis for the power network planning.

    参考文献
    相似文献
    引证文献
引用本文

徐岩,刘泽锴,应璐曼.混合MIDC馈入下的工频变化量阻抗方向保护 动作特性分析[J].电力系统保护与控制,2015,43(5):14-20.[XU Yan, LIU Zekai, YIN Luman. Performance of impedance directional protection based on variation of power-frequency components in hybrid multi-infeed HVDC system[J]. Power System Protection and Control,2015,V43(5):14-20]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2014-05-23
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2015-02-13
  • 出版日期:
文章二维码
关闭
关闭