提高变压器严重故障时差动保护动作速度的方法
CSTR:
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

基金项目:


Improving operation speed of differential protection for transformer at serious interior fault
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    分析了变压器比率差动保护动作速度慢的原因和差流速断保护在应用中遇到的问题,根据故障时差动保护中动作电流与制动电流的比值关系,提出了增加快速动作区的解决差动保护快速动作的方案,并通过数模验证了该方案能够有效提高差动保护在区内严重故障的动作速度。

    Abstract:

    By analyzing the cause of operation time of differential protection and the problem of over-current protection in application, a solution is proposed by adding the fast operation zone to improve the operation speed of transformer differential protection according to the relationship between differential current and restraint current. The numerical simulation results verify that this solution can effectively shorten the operation time of differential protection while the serious internal faults occurring.