一次110 kV线路单相断线故障的继电保护动作分析
CSTR:
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

基金项目:


Analysis of relaying operation on a single phase breakoff fault of 110 kV transmission line
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    针对我局110 kV某线路单相断线故障,通过理论公式的推导,证明了网络结构确定的110 kV线路发生单相断线故障时,其零序电流保护动作情况只取决于当时的负荷电流大小,与断线位置无关。另外,通过实际理论计算,验证了此次故障中保护及自动装置的动作行为都是正确的。

    Abstract:

    Aiming at the single phase breakoff fault happended in the 110kV Hua-Fu transmission line,some theoretical formula is deduced.It proves that the operation of zero-sequence current protection only depends on the load current and has nothing to do with the fault position,when the wire break fault happens on the 110kV transmission line in a defined network configuration.Theoretical calculation proves that the operation of relaying and automatic equipment are right in the fault.

    参考文献
    相似文献
    引证文献
引用本文

阳家书,李国友,孙建华.一次110 kV线路单相断线故障的继电保护动作分析[J].电力系统保护与控制,2007,35(22):58-60.[YANG Jia-shu, LI Guo-you, SUN Jian-hua. Analysis of relaying operation on a single phase breakoff fault of 110 kV transmission line[J]. Power System Protection and Control,2007,V35(22):58-60]