基于VMD-CNN的小电流接地系统故障电弧检测方法研究
崔朴奕1,2,李国丽1,3,张 倩1,4,范明豪5,张运勇6
(1.安徽大学电气工程与自动化学院,安徽 合肥 230601;2.教育部电能质量工程研究中心(安徽大学),安徽 合肥 230601; 3.工业节电与用电安全安徽省重点实验室(安徽大学),安徽 合肥 230601;4.工业节电与电能质量控制 安徽省级协同创新中心(安徽大学),安徽 合肥 230601;5.国网安徽省电力有限公司电力科学研究院, 安徽 合肥 230601;6.安徽北斗易通信息技术有限公司,安徽 合肥 230088)
摘要:
构建准确且符合特定场景的电弧模型,研究电弧小电流接地的电流信号特征,并基于可量测电气量信号进行处理,对于及时可靠辨识故障电弧具有重要意义。提出一种小电流接地系统故障电弧的检测方法,通过建立故障电弧模型,基于变分模态分解算法(Variational Mode Decomposition, VMD)和卷积神经网络算法(Convolution Neural Network, CNN)对故障电弧进行准确辨识。首先,采用改进“控制论”电弧模型,基于PSCAD软件平台搭建了典型10 kV配电网仿真模型和接地“控制论”电弧模型。其次,采用变分模态分解算法对故障情况下的电气信号进行处理,得到4组电流信号的固有模态分量(Intrinsic Mode Function, IMF)。然后,提取包含信号基频成分的第一组IMF(IMF1)作为卷积神经网络(CNN)的输入。最后,应用CNN对IMF1进行特征识别,正确辨识正常与电弧故障情境。实验与仿真结果显示,通过利用VMD-CNN识别方法,提高了对原始电流信号识别准确度,能准确检测出故障电弧。
关键词:  电弧模型  变分模态分解  深度卷积神经网络  故障诊断
DOI:DOI: 10.19783/j.cnki.pspc.211222
分类号:
基金项目:国家自然科学基金重点项目资助(52077001)
A fault arc detection method of a small current grounding system based on VMD-CNN
CUI Puyi1, 2, LI Guoli1, 3, ZHANG Qian1, 4, FAN Minghao5, ZHANG Yunyong6
(1. School of Electrical Engineering and Automation, Anhui University, Hefei 230601, China; 2. Engineering Research Center of Power Quality, Ministry of Education, Hefei 230601, China; 3. Anhui Key Laboratory of Industrial Energy-Saving and Safety (Anhui University), Hefei 230601, China; 4. Anhui Collaborative Innovation Center of Industrial Energy-Saving and Power Quality Control (Anhui University), Hefei 230601, China; 5. State Grid Anhui Electric Power Co., Ltd. Research Institute, Hefei 230601, China; 6. Anhui BEIDOU E-TOP Information Technology Co., Ltd., Hefei 230088, China)
Abstract:
An accurate and consistent arc model under specific scenes is built. It is important to identify a fault arc in a timely and reliable fashion by studying the current signal characteristics of arc small current grounding and processing it based on the measurable electrical volume signal. A detection method for a fault arc in a small current grounding system is proposed. By establishing the fault arc model, the fault arc is accurately identified based on variational mode decomposition and a convolution neural network. First, the improved "cybernetic" arc model is adopted, and a typical 10 kV distribution network simulation model and the grounding "cybernetic" arc model are built on the PSCAD software platform. Secondly, the variational mode decomposition algorithm is used to process the electrical signal in the fault state, and the Intrinsic Mode Function (IMF) of current signals of four groups is obtained. Then, the first set of IMF (IMF1) containing the signal fundamental frequency components is extracted as the input to the Convolutional Neural Network (CNN). Finally, CNN is used to identify the characteristics of IMF1 and correctly identify the normal and arc fault situations. The experimental and simulation results show that the VMD-CNN identification method improves the accuracy of identifying the original current signal and accurately detects the fault arc. This work is supported by the Key Project of National Natural Science Foundation of China (No. 52077001).
Key words:  arc model  variational mode decomposition  convolution neural network  fault diagnosis