基于分段拟合算法的电流互感器误差研究
周雪青1,郝晓光1,张岩坡2,赵宇皓1
(1.国网河北省电力公司电力科学研究院,河北 石家庄 050021; 2.国网河北省电力公司检修分公司,河北 石家庄 050071)
摘要:
电流互感器的传变误差直接影响继电保护动作的可靠性。然而利用现场测试数据无法直接预估大倍数短路电流时的励磁电流,很难对传变误差作定量评估和确切计算。提出利用三次样条插值和指数函数综合解析表达式,对原始数据分段处理拟合伏安特性曲线,可完整描述线性区和饱和区伏安特性,准确求出饱和区内的励磁电压和励磁电流值,从而计算出大倍数短路电流时电流互感器的传变误差和二次最大允许负载。通过与多组实测数据比对,验证了该算法拟合精度高,计算结果准确,具有较好的工程应用价值。
关键词:  电流互感器  10%误差曲线  伏安特性曲线  分段拟合
DOI:10.7667/PSPC160131
分类号:
基金项目:
Research on the error of current transformer based on subsection fitting algorithm
ZHOU Xueqing1,HAO Xiaoguang1,ZHANG Yanpo2,ZHAO Yuhao1
(1. Satae Grid Hebei Electric Power Research Institute, Shijiazhuang 050021, China;2. State Grid Hebei Electric Power Maintenance Company, Shijiazhuang 050071, China)
Abstract:
Proper transform of Current Transformer (CT) is the precondition for the proper operation of protective relays. However, the field test data can not be directly used to predict the excitation current when large short circuit current, it’s hard to make a quantitative evaluation or exact calculation of CT error. A comprehensive analytic expression of three spline interpolation and exponential function is proposed. It uses a subsection processing to fit I-V character curve, which can completely describe the linear and saturation regions of I-V character and obtain the excitation voltage and current value of the saturated region, thus it can calculate the transmission error and the maximum allowable load of the current transformer when short circuit fault occurs. After verification with the measured data, the measured data can be well fitted and the calculated results are accurate. Results show it has a good engineering application value.
Key words:  current transformer  10% error curve  V-A character curve  subsection fitting