适用电子式互感器的变压器保护磁通制动技术
徐长宝1, 高吉普1, 鲁彩江1, 王宇1, 汤汉松2, 张炜2
1.贵州电网有限责任公司电力科学研究院,贵州 贵阳 550002;2.江苏凌创电气自动化股份有限公司,江苏 镇江 212009
摘要:
为了解决传统变压器磁通制动技术在电子式互感器应用场合下的使用局限性,提出了一种适用于电子式互感器及三相变压器的磁通复判保护技术。介绍了磁通制动技术在变压器差动保护中的运用情况及存在问题,讨论了电子式互感器暂态特性对磁通制动原理的影响。研究了基于三相变压器差动保护的转角补偿、涌流选相、陷阱复判等问题,给出了保护算法实现流程。实验结果表明,适用电子式互感器的磁通制动技术能大幅提高差动保护动作速度,同时具备可靠的涌流识别能力。
关键词:  电子式互感器  变压器  差动保护  磁通制动  涌流选相
DOI:10.7667/j.issn.1674-3415.2015.18.014
分类号:
基金项目:
Flux restraint technology of transformer protection for electronic transformer
XU Changbao1, GAO Jipu1, LU Caijiang1, WANG Yu1, TANG Hansong2, ZHANG Wei2
1.Electric Power Research Institute of Guizhou Power Grid Co., Ltd., Guiyang 550002, China;2.Jiangsu Lingchuang Electric Automation Co., Ltd., Zhenjiang 212009, China
Abstract:
In order to solve the limitations of traditional transformer flux restraint technology in electronic transformer application, this paper proposes a flux complex judgment technology for electronic transformer and three-phase transformer. The application situation and the existing problems of flux restraint technology are introduced in transformer differential protection, the influence of transient characteristics of electronic transformer on flux restraint theory is discussed, the problems of angle compensation, inrush current phase selection, trap multiple identification which are used in differential protection of three-phase transformer are researched, and the algorithm implementation process is given. Experiments show that flux restraint theory for electronic transformer can greatly improve the speed of the action of differential protection, and has the reliable identification ability for inrush current.
Key words:  electronic transformer  transformer  differential protection  flux restraint  inrush current phase selection