Fault identification scheme for protection and adaptive reclosing in a hybrid multi-terminal HVDC system
DOI:10.1186/s41601-023-00297-8
Key Words:Adaptive reclosing, Hybrid multi-terminal HVDC system, Protection, Signal injection
Author NameAffiliation
Junjie Hou  
Guobing Song  
Yanfang Fan  
Hits: 2325
Download times: 0
Abstract:A fault identification scheme for protection and adaptive reclosing is proposed for a hybrid multi-terminal HVDC system to increase the reliability of fault isolation and reclosing. By analyzing the "zero passing" characteristic of current at the local end during the converter capacitor discharge stage, the fault identification scheme is proposed. The distributed parameter-based fault location equation, which incorporates fault distance and fault impedance, is developed with the injection signal and the distributed parameter model during the adaptive reclosing stage. The fault distance is determined using a trust region reflection algorithm to identify the permanent fault, and a fault identification scheme for adaptive reclosing is developed. Simulation results show that the proposed scheme is suitable for long-distance transmission lines with strong anti-fault impedance and anti-interference performance. Also, it is less affected by communication delay and DC boundary strength than existing methods.
View Full Text  View/Add Comment  Download reader