Analysis of the arc high impedance grounding faults voltage characteristics in non-effective grounding feeders 4. State Grid Liaoning Electric Power Research Institute, Shenyang 110003, China)
DOI:10.19783/j.cnki.pspc.181088
Key Words:small current grounding  distribution lines  arc  high impedance grounding  zero sequence voltage
Author NameAffiliation
QIU Jin 中国电力科学研究院有限公司北京 100192
电网环境保护国家重点实验室湖北 武汉 430074 
CUI Xin 电力系统及发电设备控制和仿真国家重点实验室清华大学电机系北京 100084 
TIAN Ye 中国电力科学研究院有限公司北京 100192
国网辽宁省电力有限公司电力科学研究院辽宁 沈阳 110003 
WANG Bin 电力系统及发电设备控制和仿真国家重点实验室清华大学电机系北京 100084 
LI Guanhua 国网辽宁省电力有限公司电力科学研究院辽宁 沈阳 110003 
Hits: 3329
Download times: 1286
Abstract:The difficulty of single-phase arc high impedance grounding fault detection in neutral ineffectively grounded system lies in how to realize sensitive start. The current detection methods use the zero sequence voltage amplitude limit as the starting criterion, but the setting of the limit value directly affects the sensitivity and reliability of detection, it is often difficult to take into account both in practical operation. Aiming at this problem, based on the field wave recording data, this paper analyzes the transient voltage characteristics in the event of the single-phase arc high impedance grounding fault by means of numerical statistics, Fourier transform and graph comparison from the time domain and frequency domain. Meanwhile, the transient model of arc high impedance grounding fault is established, which verifies the validity of the transient voltage characteristics features extracted. It lays a foundation for the subsequent development of sensitive start criterion of faulty line selection device when single-phase arc high impedance grounding fault occurs. This work is supported by Science and Technology Project of the Headquarters of State Grid Corporation of China (No. GY71-17-032) “Study on Multi-State Complex Fault Feature Library and Key Technology of Adaptive Identification in Distribution Networks”.
View Full Text  View/Add Comment  Download reader