Application and study of LMS adaptive filter in AC filter protection of Yan Huai UHVDC power transmission project
DOI:10.7667/PSPC171779
Key Words:C1 capacitor  unbalance protection  initial unbalanced current  LMS adaptive filter  HCM3000
Author NameAffiliation
LIU Weipeng XJ Electric Co., Ltd., Xuchang 461000, China 
ZENG Lili XJ Electric Co., Ltd., Xuchang 461000, China 
ZHANG Ailing XJ Electric Co., Ltd., Xuchang 461000, China 
ZHANG Jian XJ Electric Co., Ltd., Xuchang 461000, China 
LUO Lei XJ Electric Co., Ltd., Xuchang 461000, China 
Hits: 2884
Download times: 1372
Abstract:Taking the unbalanced current correction of AC filter protection system in Yan Huai HVDC project as the object of study, the structure of the high-voltage capacitor bank and the principle of unbalanced protection are introduced. The importance and significance of unbalanced current correction are clarified. It is unreasonable to point out that the initial unbalanced current used in the traditional method does not fully take into account the fluctuation of its phase and amplitude. In view of the randomness of the initial unbalanced current, the principle and characteristics of LMS adaptive filter are introduced, and its implementation in HCM3000 platform are given. The key parameters of filter are researched and given, and the method of application in specific engineering is expounded. The engineering data verify the rationality of the design and the superiority of the performance. This work is supported by National Key Research and Development Program of China (No. 2016YFB0900600) “Operation Control and Protection of Large-scale AC/DC Hybrid-connected Power Grid”
View Full Text  View/Add Comment  Download reader