A correction of ground short-circuit criterion of phase selection element based on faulty components
DOI:10.7667/PSPC171053
Key Words:faulty component  phase selection element  ground short-circuit  current phase  distribution factor
Author NameAffiliationE-mail
CHENG Zhiyou Power Quality Engineering Research Center, Ministry of Education, Hefei 230601, China
School of Electronics and Information Engineering, Anhui University, Hefei 230601, China 
 
LI Xiaojing School of Electronics and Information Engineering, Anhui University, Hefei 230601, China lixiaojing0007@126.com 
TANG Mingjin School of Electronics and Information Engineering, Anhui University, Hefei 230601, China  
XIA Shuang School of Electronics and Information Engineering, Anhui University, Hefei 230601, China  
Hits: 2897
Download times: 1200
Abstract:Based on the detailed analysis of fault component phase selection principle, the traditional ground short-circuit criterion of phase selection element based on faulty components is improved. The improved criterion only uses the phase difference between the negative sequence faulty components current phase and the positive sequence faulty components current phase and adds the threshold judgment of the zero sequence voltage component to distinguish the ground fault. It avoids the shortcomings of misjudgment since the zero sequence current distribution factor is not equal to its positive and negative ones in the traditional ground short-circuit criteria as well as simplifies the phase selection process. Simulation results show that the improved criterion is valid and stable. This work is supported by National Natural Science Foundation of China (No. 6172032).