Author Name | Affiliation | E-mail | ZHANG Linli | State Grid Shandong Electric Power Research Institute, Jinan 250003, China | | CAO Lili | College of Information and Control Engineering, China University of Petroleum East China, Qingdao 266580, China | | LI Lisheng | State Grid Shandong Electric Power Research Institute, Jinan 250003, China | lls@sina.com | XUE Yongduan | College of Information and Control Engineering, China University of Petroleum East China, Qingdao 266580, China | | TIAN Ye | State Grid Dongying Power Supply Company, Dongying 257091, China | | FENG Guang | Electric Power Research Institute of State Grid Henan Electric Power Company, Zhengzhou 450052, China | |
|
Hits: 4063 |
Download times: 2068 |
Abstract:Due to the application of insulated wire, the occurrence probability of line break faults in distribution lines increases. There are no effective method to detect line break fault on site. In this paper, based on ungrounding system, a model of single-phase line break fault without grounding is established. Line break location, the ratio of the fault line grounding capacitance to system grounding capacitance, load impedance magnitude and distribution factors are taken into consideration. Variation characteristics of offset voltage at neutral point, line voltage and phase voltage of the line break point are analyzed. According to the variation characteristics of line voltage and phase voltage, this paper proposes fault section location methods respectively to detect single-phase line break fault without grounding. This proposed method can be realized through distribution automation platform or malfunction indicator system, which improves the reliability and applicability of line break fault section location. In the end, this method is verified by Matlab simulation. This work is supported by National Natural Science Foundation of China (No. 51477184). |
View Full Text View/Add Comment Download reader |
|
|
|