摘要: |
超高压输电系统中,存在单间隔或多间隔线路差动主保护丢失后后备保护在线路区内故障时可能存在动作延时长、失配导致的误动或拒动风险。针对单间隔或多间隔线路保护装置闭锁、通信设备异常、通信通道故障导致的线路差动主保护丢失工况,分析了后备保护的适应性,提出了基于站域开关量信息采集来判断不同工况导致主保护丢失的识别逻辑。并制定了基于站域共享信息的后备保护主动和被动加速自调整应急优化方案,缩短后备保护的动作时间和自适应调整后备保护的动作范围,并通过仿真验证。仿真表明,优化后的应急后备保护实现线路差动主保护丢失后由距离保护和零序保护快速有序切除故障。 |
关键词: 主保护丢失 后备保护 闭锁 加速自调整 通道故障 差动 |
DOI:DOI: 10.19783/j.cnki.pspc.200735 |
投稿时间:2020-06-28修订日期:2020-09-12 |
基金项目:国家电网公司华中分部科技项目资助(SGH80000DKJS1900219); 国家电网公司总部科技项目资助(5100-201919020A-0-0-00) |
|
Emergency plan for backup protection against loss of line differential main protection |
WANG Yingying1,2,JIN Mingliang1,2,WANG Yulong3,XIE Jun1,2,ZHAO Qingchun3,CHEN Xiangwen1,2 |
(1. Central China Branch of State Grid Corporation of China, Wuhan 430000, China; 2. Lamor Innovation Studio of
Liu Huanzhang, Wuhan 430000, China; 3. NARI-Relays Electric Co., Ltd., Nanjing 211102, China) |
Abstract: |
In a UHV transmission system, there is an abnormal working condition in which the single or multiple interval line differential main protections are lost. If the fault protection in the line area after the main protection is lost, there may be a long action delay, mismatch or mis-operation risk caused by mismatch. The adaptability of back-up protection is analyzed in view of the loss of line differential main protection caused by single or multiple line protection device blocking, communication equipment abnormalities and communication channel failure. An identification logic, for judging the loss of main protection caused by different operating conditions, based on the collection of switch information in the substation domain is proposed. An emergency optimization plan for active and passive acceleration self-adjustment of backup protection based on the shared information of the station domain is formulated to shorten the operation time of the backup protection and adaptively adjust the range of the backup protection. This is verified by simulation. The simulation shows that the optimized emergency backup protection shows that distance protection and zero sequence protection can quickly and, in an orderly fashion, remove the faults after line differential main protection is lost.
This work is supported by the Science and Technology Project of State Grid Central China Branch (No. SGH80000DKJS1900219) and the Science and Technology Project of the Headquarters of State Grid Corporation of China (No. 5100-201919020A-0-0-00). |
Key words: loss of main protection backup protection blocking acceleration self-adjustment channel failure differential protection |